06/02/2006
Clearances Over Areas and Buildings:
Per the National Electrical Safety Code (NESC), cabled service drop, 600 Volts and less, shall have a minimum clearance above:
NOTES:
1 Limited to 300 Volts to ground.
2 Limited to 150 Volts to ground.
3 Conductors attached to building.
4 Where service does not pass over more than 48 inches horizontal of the overhang/eaves portion of the roof, and the service is terminated at a through-the-roof raceway or approved support.
5 Where service does not pass over more than 72 inches horizontal of the overhang/eaves portion of the roof, and the service is terminated at a through-the-roof raceway or approved support.
Clearance Under Communication Company Lines
Where a service drop crosses under communication conductors, cables, or messengers which are on different supporting structures, the vertical clearance shall be 24 inches minimum.
Clearances Between Gas Facilities and Electric Meters
These required separations are taken from the NFPA National Fuel Gas Code Section 5.7.2.3 and NFPA Liquefied Petroleum Gas Code Table 3.2.2.2 (d):
See Sketch #55
Clearances Between Satellite Dish and PPL EU Facilities